fieldcommunicator

Yokogawa AAV144-S50/K4A00 AAV144-H53/A4S00 Input Module Arri

Yokogawa AAV144-S50/K4A00 AAV144-H53/A4S00 Input Module Arrived

Yokogawa AAV144-S50/K4A00 AAV144-H53/A4S00 Input Module Arrived

 

 

Model and Suffix Codes of AAV144

 

 

   

Description

Model

AAV144

Analog Input Module (-10 to +10 V, 16-channel, Isolated)

 

Suffix Codes

-S

Standard type

5

With no explosion protection

E

With explosion protection

0

Basic type

3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

 

 

Option Codes

/K4A00

With KS Cable Interface Adapter [Model: ATK4A-00]

/A4S00

With Pressure Clamp Terminal Block for Analog [Model: ATA4S-00]

/A4S10

With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10]

/A4D00

With Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00]

/A4D10

With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10]

/CCC01

With Connector Cover for MIL Cable [Model: ACCC01]

 

External Dimensions of AAV144

 

 

image

 

 

 

 

Voltage Input Module (Isolated)

 

This module is for 16 inputs of 1 to 5 V or -10 to 10 V signal.  It can be used in dual-redundant configuration.

 

Items

Specifications

Model

AAV144

Number of input channels

16, isolated

Input signal

1 to 5 V

-10 to 10 V

Switching input signals

Input signals can be set together for CH1 to CH16

Allowable input voltage

±30 V

Withstanding isolated voltage

Between input and system: 1500 VAC withstanding voltage, for 1 minute (*1)

Input resistance

Power ON

1 MΩ

Power OFF

200 kΩ

Accuracy

±4 mV

±20 mV

Data update period

10 ms

Drift due to ambient temperature change

±4 mV/10 ˚C

±20 mV/10 ˚C

Maximum current consumption

500 mA (5 V DC)

Weight

0.2 kg

External communication

Pressure clamp terminal, MIL connector cable, dedicated cable (KS1)

*1:      When the dedicated cable is used, the withstanding voltage is 500 VAC (between the input signal and the system). When the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.



 

AAV144:
 

 

AAV144-S50/K4A00, AAV144-S50/A4S00, AAV144-S50/A4S10, AAV144-S50/A4D00, AAV144-S50/A4D10, AAV144-S50/CCC01

 

AAV144-S53/K4A00, AAV144-S53/A4S00, AAV144-S53/A4S10, AAV144-S53/A4D00, AAV144-S53/A4D10, AAV144-S53/CCC01

 

AAV144-SE0/K4A00, AAV144-SE0/A4S00, AAV144-SE0/A4S10, AAV144-SE0/A4D00, AAV144-SE0/A4D10, AAV144-SE0/CCC01

 

AAV144-SE3/K4A00, AAV144-SE3/A4S00, AAV144-SE3/A4S10, AAV144-SE3/A4D00, AAV144-SE3/A4D10, AAV144-SE3/CCC01

 

AAV144-H50/K4A00, AAV144-H50/A4S00, AAV144-H50/A4S10, AAV144-H50/A4D00, AAV144-H50/A4D10, AAV144-H50/CCC01

 

AAV144-H53/K4A00, AAV144-H53/A4S00, AAV144-H53/A4S10, AAV144-H53/A4D00, AAV144-H53/A4D10, AAV144-H53/CCC01

 

AAV144-HE0/K4A00, AAV144-HE0/A4S00, AAV144-HE0/A4S10, AAV144-HE0/A4D00, AAV144-HE0/A4D10, AAV144-HE0/CCC01

 

AAV144-HE3/K4A00, AAV144-HE3/A4S00, AAV144-HE3/A4S10, AAV144-HE3/A4D00, AAV144-HE3/A4D10, AAV144-HE3/CCC01

 

 

 

We mainly supply Yokogawa,Emerson, Rosemount,Fisher,Honeywell,Siemens, ABB,FLUKE, Schneider Electric, Pepperl+Fuchs,MTL,Rockwell(Allen Bradley), Hirschmann, Eaton ,Moeller,FUJI,Omron, Yaskawa,Norgren,CHINT,Hach,Weidmuller,Phoenix, SMC,Testo, ASCO,Parker,Mitsubishi, Festo,GE, CISCO,Auma,IFM,GM,Turck,MOXA, Foxboro, Krohne, Swagelok, LS, Advantech, Dwyer,Endress Hauser, Bently Nevada,Moog etc.

 

We are specialized in intelligent instruments, including : Transmitters, Flowmeters, Analyzers,Communicators, Safety Barriers, Sensors,Gas Detectors, PLC(DCS), Multimeters, Calibrators, Communicators, Recorder, Inverters, Positioners, Valves, Soft Starters, Circuit Breakers, Contactors, Rail Switches, Power Supply, HMI, Terminal Block, Relay etc.

 

Contact:

HONGKONG XIEYUAN TECH CO., LIMITED
Email:becky@hkxytech.com   Web:www.hkxytech.com
Mobile:+86-15972186287(Whatsapp & Wechat) 

 

 

 

 

Previous:Yokogawa AAI543-H53/K4A00 AAI543-S50/A4S00 Output Module Arr Next:Yokogawa AAV544-H53/K4A00 AAV544-S53/A4S10 DCS Module Arrive
 Footer begin -->